Regulation 366

The engineering manager of a mine shall ensure that in the mine 
(a) a suitable method of earth leakage protection is provided for all alternating current circuits except for circuits below extra low voltage;
(b) earth leakage protection equipment
(i) is provided with means by which tests of the operation of the equipment may be made;
(ii) is rated to isolate the power supply at not more than five hundred milli-ampere of leakage current; and 
(iii) is provided for a circuit supplying portable apparatus and shall operate at a leakage current not exceeding thirty mill amperes (mA).